  • Abstract
    The fast and very fast transient overvoltages can endanger the insulation of transformer windings. Therefore, it is necessary to develop models, to study these transients. This paper compares the two well-known multiconductor transmission line (MTL) and lumped parameter detailed (RLC ladder network) models. The high-voltage (HV) winding of a 220/35-kV, 50-MVA transformer has been modeled using these models. The simulation results of the MTL and the RLC ladder network models have been compared with the measurements results in the frequency domain, by application of the Pearson´s correlation coefficients. It is shown that the RLC Ladder Network model should be used for fast transient overvoltage (FTO) studies, i.e. frequency range of 10 kHz < / < 1 MHz and the MTL model with frequency dependent loss factor, demonstrates a better agreement with the measurement results for very fast transient overvoltage (VFTO) studies, i.e., in the frequency range of 1 MHz les / les 5 MHz.
  • Keywords
    power transformer insulation; transformer windings; RLC ladder network; frequency dependent loss factor; high-voltage winding; multiconductor transmission line; transformer windings insulation; very fast transient overvoltages; voltage 220 kV; voltage 35 kV; Loss factor; modeling; multiconductor transmission line; power transformer; very fast transient;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2008.915795
  • Filename
    4443847