DocumentCode
1051571
Title
Sparkover Characteristics of High Voltage Protective Gaps
Author
Group, I.W.
Issue
1
fYear
1974
Firstpage
196
Lastpage
205
Abstract
Published data on sparkover characteristics of high-voltage protective gaps with 50-200 cm spacings have been reviewed and statistically analyzed. The results are presented, including: volt-time curves for times to sparkover up to 8 Ms, average critical sparkover gradient for various types of gaps for lightning impulse and for switching impulse, and average sparkover gradient for power-frequency voltage. Wherever justifiable, 95 percent confidence intervals are also given.
Keywords
Breakdown voltage; Circuit testing; Equations; Impedance; Insulation; Lightning; Shape; Substation protection; Surge Protective Devices - c62; Voltage control;