Title :
Voltage Escalation in Interrupting Inductive Current by Vaccum Switches
Author :
Murano, M. ; Fujii, T. ; Nishikawa, H. ; Nishiwaki, S. ; Okawa, M.
Author_Institution :
Tokyo Shibaura Electric Company, Ltd.
Abstract :
The paper relates the voltage escalation due to repetitive reignition occurring when interrupting the inductive current by vacuum switches, and offers a new theory quite different from those recognized hitherto on the generating mechanism. It also shows that a CR Surge Suppressor is effective for suppressing the voltage escalation.
Keywords :
Chromium; Circuit testing; Coaxial cables; Contacts; Dielectrics; Induction motors; Surges; Switches; Switching circuits; Voltage control;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1974.293942