Title : 
Coefficient of Variation of the Positive-Impulse Breakdown of Long Air-Gaps
         
        
            Author : 
Menemenlis, C. ; Harbec, G.
         
        
            Author_Institution : 
Hydro-Québec Institute of Research
         
        
        
        
            fDate : 
5/1/1974 12:00:00 AM
         
        
        
        
            Abstract : 
Extensive impulse breakdown tests on long air-gaps show that the coefficient of variation C = ¿/U50% à 100% depends on the form of the impulse. Tests were performed on three different gaps of 3, 5.90 and 8.75 meters long. The value of C for each form of the impulse was estimated by applying approximately 700 shots at appropriate voltage levels. The procedure used allowed C to be estimated with a confidence interval, at the 95% level, in the order of ±0.1 C.
         
        
            Keywords : 
Air gaps; Breakdown voltage; Conductors; Electric breakdown; Gunshot detection systems; Impulse testing; Performance evaluation; Power systems; System testing; Voltmeters;
         
        
        
            Journal_Title : 
Power Apparatus and Systems, IEEE Transactions on
         
        
        
        
        
            DOI : 
10.1109/TPAS.1974.294011