DocumentCode
1052570
Title
Coefficient of Variation of the Positive-Impulse Breakdown of Long Air-Gaps
Author
Menemenlis, C. ; Harbec, G.
Author_Institution
Hydro-Québec Institute of Research
Issue
3
fYear
1974
fDate
5/1/1974 12:00:00 AM
Firstpage
916
Lastpage
927
Abstract
Extensive impulse breakdown tests on long air-gaps show that the coefficient of variation C = ¿/U50% à 100% depends on the form of the impulse. Tests were performed on three different gaps of 3, 5.90 and 8.75 meters long. The value of C for each form of the impulse was estimated by applying approximately 700 shots at appropriate voltage levels. The procedure used allowed C to be estimated with a confidence interval, at the 95% level, in the order of ±0.1 C.
Keywords
Air gaps; Breakdown voltage; Conductors; Electric breakdown; Gunshot detection systems; Impulse testing; Performance evaluation; Power systems; System testing; Voltmeters;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1974.294011
Filename
4075437
Link To Document