Title :
A Half Cycle Bus Differential Relay and its Application
Author :
Forford, T. ; Linders, J.R.
Author_Institution :
ASEA
fDate :
7/1/1974 12:00:00 AM
Abstract :
The principles of a new high speed bus differential relay which operates for an internal fault condition within 1 to 2 ms and initiates tripping of circuit breakers in about 7 ms is described. The relay is self-powered and requires no auxiliary voltage other than that needed for the output tripping and alarm functions. It is shown to be insensitive to remanence and saturation of current transformers and to systems fault levels and X/R ratios.
Keywords :
Circuit faults; Couplers; Current transformers; Fault currents; Impedance; Power system protection; Power system relaying; Protective relaying; Relays; Testing;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1974.294057