• DocumentCode
    1052856
  • Title

    A Half Cycle Bus Differential Relay and its Application

  • Author

    Forford, T. ; Linders, J.R.

  • Author_Institution
    ASEA
  • Issue
    4
  • fYear
    1974
  • fDate
    7/1/1974 12:00:00 AM
  • Firstpage
    1110
  • Lastpage
    1120
  • Abstract
    The principles of a new high speed bus differential relay which operates for an internal fault condition within 1 to 2 ms and initiates tripping of circuit breakers in about 7 ms is described. The relay is self-powered and requires no auxiliary voltage other than that needed for the output tripping and alarm functions. It is shown to be insensitive to remanence and saturation of current transformers and to systems fault levels and X/R ratios.
  • Keywords
    Circuit faults; Couplers; Current transformers; Fault currents; Impedance; Power system protection; Power system relaying; Protective relaying; Relays; Testing;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1974.294057
  • Filename
    4075467