DocumentCode :
1053109
Title :
Harmonic measurements from a group connected generator HVDC converter scheme
Author :
Macdonald, S.J. ; Enright, W. ; Arillaga, J. ; O´Brien, M.T.
Author_Institution :
Canterbury Univ., Christchurch, New Zealand
Volume :
10
Issue :
4
fYear :
1995
fDate :
10/1/1995 12:00:00 AM
Firstpage :
1937
Lastpage :
1943
Abstract :
A recent CIGRE document published in ELECTRA has described the potential benefits of a direct connection of generators to HVDC power converters. While many theoretical contributions have been made, no practical test data has become available so far. This paper reports on harmonic tests carried out at the Benmore end of the New Zealand HVDC link operating as a group connected scheme. It was found that the measured harmonic current levels were well below specified generator ratings. Dynamic simulation accurately predicted the harmonic currents whereas the results of a steady state formulation were less-reliable
Keywords :
DC transmission networks; HVDC power convertors; HVDC power transmission; electric generators; harmonic distortion; power system harmonics; power system measurement; HVDC power converters; New Zealand; generator ratings; group connected generator; harmonic current levels; harmonic measurements; harmonic tests; Active filters; Costs; HVDC transmission; Power generation; Power harmonic filters; Power system harmonics; Stator windings; Steady-state; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.473360
Filename :
473360
Link To Document :
بازگشت