Title :
Dynamic Stability Tests on a 733 MVA Generator at Kincaid Station
Author :
Bingen, P. ; Landgren, G.L. ; Keay, F.W. ; Raczkowski, C.
Author_Institution :
Commonwealth Edison Company
Abstract :
Field tests have confirmed that properly designed excitation control can extend the dynamic stablity range of machines. A new type of stability compensation, described in a companion paper, has been successfully applied. Application of this new equipment is made possible by the installation of a modern solid state high performance excitation system. Field tests conducted on a 733 mVA generator have shown that this compensation, applied to the excitation system, is effective in extending the stability limit of the machine beyond the limit obtainable without compensation.
Keywords :
Control systems; Impedance; Low voltage; Manufacturing; Regulators; Sliding mode control; Solid state circuits; Stability; System testing; Voltage control;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :