DocumentCode :
1053235
Title :
The Front Shape of Switching Impulses and its Effect on Breakdown Parameters
Author :
Menemenlis, C. ; Isaksson, K.
Author_Institution :
Hydro-Québec Institute of Research
Issue :
5
fYear :
1974
Firstpage :
1380
Lastpage :
1389
Abstract :
A 3-meter rod-plane gap was tested with double exponential switching impulses of different front times. The front of each of the impulses was subsequently modified so that it rose steeply to a certain level of the original front and then followed the basic non-modified impulse. This front modification made it possible to study the influence each region of the front has on the 50% breakdown voltage and the standard deviation of air-gaps. From the results obtained it was possible to detect the region of the front which mainly affects the breakdown parameters. Based on these results, a new definition of the switching-impulse front is proposed providing concrete information about the response of a gap when subjected to an impulse with a given front.
Keywords :
Air gaps; Breakdown voltage; Concrete; Electric breakdown; IEC standards; Impulse testing; Laboratories; Performance evaluation; Shape measurement; Stress measurement;
fLanguage :
English