• DocumentCode
    1053403
  • Title

    A new method of harmonic power detection based on the instantaneous active power in three-phase circuits

  • Author

    Tanaka, Toshihiko ; Akagi, Hirofumi

  • Author_Institution
    Polytechnic Univ., Sagamihara, Japan
  • Volume
    10
  • Issue
    4
  • fYear
    1995
  • fDate
    10/1/1995 12:00:00 AM
  • Firstpage
    1737
  • Lastpage
    1742
  • Abstract
    This paper presents a new method of harmonic power detection based on the instantaneous active power in three-phase circuits, and its applications to search for dominant harmonic sources in power systems. The proposed method requires only band elimination filters and a three-phase active power meter to detect the harmonic active power, and it is able to deal with harmonic power flow more easily and precisely than a conventional meter which is based on Fourier series of single-phase circuits. In addition, measurement errors of the harmonic power are discussed theoretically. The validity of the proposed method is demonstrated by digital simulation
  • Keywords
    harmonic distortion; measurement errors; measurement theory; power filters; power measurement; power meters; power system analysis computing; power system harmonics; power system measurement; active power meter; band elimination filters; digital simulation; dominant harmonic sources; harmonic power detection; harmonic power flow; instantaneous active power; measurement errors; three-phase power systems; Active filters; Circuits; Load flow; Measurement errors; Passive filters; Power harmonic filters; Power system harmonics; Power system measurements; Pulse power systems; Thyristors;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.473386
  • Filename
    473386