DocumentCode
1053805
Title
Shunt Capacitor Switching EMI Voltages, Their Reduction in Bonneville Power Administration Substations
Author
Rogers, Eldon J. ; Gillies, Don A.
Author_Institution
Bonneville Power Adrministration
Issue
6
fYear
1974
Firstpage
1849
Lastpage
1860
Abstract
Back to back switching of grounded Wye shunt capacitors cause high frequency, high magnitude current flow in overhead bus and ground mat conductors. Measurements of induced voltages on control cables and receptacles, transverse voltages on fuse blown PT secondaries and personnel intercept voltages are reported. BPA methods of confining transients to capacitor areas and shielding techniques are reviewed.
Keywords
Capacitance; Capacitors; Circuits; Conductors; Electromagnetic interference; Frequency; Personnel; Substations; Switches; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1974.293838
Filename
4075557
Link To Document