AC/DC harmonic interactions in the presence of GIC for the Quebec-New England Phase II HVDC transmission
Author
Dickmander, D.L. ; Lee, S.Y. ; Désilets, G.L. ; Granger, M.
Author_Institution
ABB Transmission Technol. Inst., Raleigh, NC, USA
Volume
9
Issue
1
fYear
1994
fDate
1/1/1994 12:00:00 AM
Firstpage
68
Lastpage
78
Abstract
During the spring of 1991, several severe geomagnetic disturbances were recorded in North America, and particularly in Northern Quebec, where Hydro-Quebec´s La Grande generation complex and transmission system are located. As a result of these disturbances, the Quebec-New England Phase II HVDC system was affected by transformer saturation and harmonic voltage distortion due to geomagnetic induced current (GIC). This paper presents an analysis of the phenomenon observed at Radisson, the northernmost terminal in the system. A central issue which is discussed in the paper is the reflection of the DC side impedance to the AC side for operating converters, and the effect of this reflection on the harmonic impedance as viewed from the AC side
Keywords
DC power transmission; autotransformers; electric impedance; geomagnetism; power system harmonics; AC/DC harmonic interactions; DC side impedance reflection; GIC; Hydro-Quebec´s La Grande generation complex; North America; Northern Quebec; Quebec-New England Phase II HVDC transmission; Radisson; autotransformers; geomagnetic disturbances; geomagnetic induced current; harmonic impedance; harmonic voltage distortion; transformer saturation; Analog-digital conversion; Circuit faults; Geomagnetism; HVDC transmission; Harmonic distortion; Impedance; North America; Phase distortion; Reflection; Springs;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.277681
Filename
277681
Link To Document