Title :
Long-term reliability of amorphous alloy wound core distribution transformers
Author :
Ezure, S. ; Imai, Y. ; Sato, H. ; Yamada, S. ; Yamanaka, K. ; Saito, S.
Author_Institution :
Tokyo Electr. Power Co. Inc., Japan
fDate :
1/1/1994 12:00:00 AM
Abstract :
In order to verify long-term reliability of amorphous alloy wound core distribution transformers, accelerated aging tests and field trials used on actual transformers were practised. As for accelerated aging tests, short-circuit tests were added to imitate mechanical stress in operation on a utility´s distribution system. As a result, even after the equivalent of 30 years, which was the normal expected transformer´s life, the magnetic characteristic was unchanged, so these transformers could be operated. Additionally, two hundred transformers of four kinds were installed on a utility´s distribution system to study no-load characteristics. They were equipped with a mechanism to measure load current, background vibration and lightning surge current, so their influence on magnetic characteristic could be inspected. As a result, no remarkable change was seen even after six months
Keywords :
ageing; distribution networks; life testing; power system reliability; power transformers; transformer cores; transformer testing; accelerated aging tests; amorphous alloy; background vibration; distribution system; electric utilities; field trials; lightning surge current; load current; long-term reliability; magnetic characteristic; mechanical stress; no-load characteristics; short-circuit tests; wound core distribution transformers; Accelerated aging; Amorphous magnetic materials; Amorphous materials; Current measurement; Lightning; Stress; System testing; Transformer cores; Vibration measurement; Wounds;
Journal_Title :
Power Delivery, IEEE Transactions on