• DocumentCode
    1055504
  • Title

    A new relay for interconnected distribution in the UK-design and field experience

  • Author

    Sanderson, J.V.H. ; Kyriakides, M.K. ; An, Wen ; Mackrell, A.J. ; Lethwai, H. R Post ; Rogers, W.J.S. ; Swinnerton, B.W.

  • Author_Institution
    Power Eng. Consultants Ltd., Alderley Edge, UK
  • Volume
    9
  • Issue
    1
  • fYear
    1994
  • fDate
    1/1/1994 12:00:00 AM
  • Firstpage
    453
  • Lastpage
    460
  • Abstract
    The design of a new microprocessor based multifunctional relay for use on interconnected 33 kV circuits is described. The relay uses sequence component principles and rented low grade VF communication. It was needed urgently because rented metallic communication circuits, which are in widespread use, are being withdrawn in the UK. The relay development is unusual because of its measurement methods and because it can derive polarising voltage from existing 11 kV VTs. The time scales required were such that development, field trials and installation phases overlapped. The field experience is described
  • Keywords
    distribution networks; microcomputer applications; power engineering computing; power system protection; relay protection; 33 kV; UK; interconnected distribution; low grade VF communication; microprocessor based multifunctional relay; polarising voltage; sequence component principles; Circuit faults; Communication channels; Earth; Integrated circuit interconnections; Microprocessors; Power system protection; Protective relaying; Relays; Switches; Telecommunications;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.277717
  • Filename
    277717