DocumentCode
1058552
Title
Testing of 3-Meter Prototype Fault Current Limiting Cables
Author
Gouge, Michael J. ; Duckworth, R.C. ; Demko, J.A. ; Rey, C.M. ; Thompson, J.R. ; Lindsay, D.L. ; Tolbert, J.C. ; Willen, D. ; Lentge, H. ; Thidemann, C. ; Kledal, I.D. ; Carter, W.L.
Author_Institution
Oak Ridge Nat. Lab., Oak Ridge, TN, USA
Volume
19
Issue
3
fYear
2009
fDate
6/1/2009 12:00:00 AM
Firstpage
1744
Lastpage
1747
Abstract
Two 3-m long, single-phase cables have been fabricated by Ultera from second generation (2G) superconductor wire supplied by American Superconductor. The first cable was made with two layers of 2G tape conductor and had a critical current of 5,750 A while the second cable had four layers and a critical current of 8,500 A. AC loss was measured for both cables at ac currents of up to 4 kArms. Ultera performed initial fault current studies of both cables in Denmark with limited currents in the range from 9.1 to 44 kA. Results from these tests will provide a basis for a 25-m long, three-phase, prototype cable to be tested at ORNL early next year and a 300-m long, fault current limiting, superconducting cable to be installed in a Consolidated Edison substation in New York City.
Keywords
fault current limiters; power cable testing; superconducting cables; American Superconductor; Consolidated Edison substation; current 4 kA; current 5750 A; current 8500 A; current 9.1 kA to 44 kA; distance 3 m; distance 300 m; prototype fault current limiting cables; second generation superconductor wire; superconducting cable; High-temperature superconductors; power transmission lines; superconducting cables;
fLanguage
English
Journal_Title
Applied Superconductivity, IEEE Transactions on
Publisher
ieee
ISSN
1051-8223
Type
jour
DOI
10.1109/TASC.2009.2018310