DocumentCode :
1061241
Title :
Fault Current Limiter Using YBCO Coated Conductor—The Limiting Factor and Its Recovery Time
Author :
Baldan, Carlos A. ; Lamas, Jérika Suely ; Shigue, Carlos Yujiro ; Filho, Ernesto Ruppert
Volume :
19
Issue :
3
fYear :
2009
fDate :
6/1/2009 12:00:00 AM
Firstpage :
1810
Lastpage :
1813
Abstract :
A fault current limiter (FCL) based on an arrangement of parallel connected high temperature superconducting tapes constituting a limiter element was designed and tested in 220 V line for a fault current peak between 1 kA to 2 kA. The limiter employed second generation (2G) HTS tapes of YBCO coated conductor reinforced with stainless steel. Four tapes were electrically connected in parallel with 0.4 m effective length per element wherein 16 elements connected in series constitutes a single-phase unit. The FCL performance was evaluated through over-current and current fault tests. Its recovery characteristics were used to design the shunt protection. The designed limiting ratio is 4 for 16 elements and the experimental result for one element showed a 20% limiting ratio. For the fault current test one element can withstand five cycles of fault without degradation. It was observed recovery times below 0.5 s under nominal load using a shunt resistance of 173 mOmega.
Keywords :
fault current limiters; high-temperature superconductors; superconducting tapes; 2G HTS tapes; YBa2Cu3O7; conductor; current fault tests; fault current limiter; high temperature superconducting tapes; recovery time; resistance 173 mohm; stainless steel; voltage 220 V; Current limiting ratio; YBCO coated conductor; YBCO recovery characteristics; superconducting fault current limiter;
fLanguage :
English
Journal_Title :
Applied Superconductivity, IEEE Transactions on
Publisher :
ieee
ISSN :
1051-8223
Type :
jour
DOI :
10.1109/TASC.2009.2019043
Filename :
5067233
Link To Document :
بازگشت