Abstract :
A negative-sequence current produced during the single-phasing condition of a three-phase induction motor does not allow the motor to start and creates excessive heating while running. To eliminate the negative-sequence current, and thus to operate the motor satisfactorily under a single-phasing condition, the student is to connect a zigzag winding transformer with its star point connected to a system neutral across the motor. This experiment provides a thorough understanding of the sequence network connections under the single-phasing condition of a three-phase induction motor.
Keywords :
electrical engineering education; induction motors; student experiments; transformer windings; negative-sequence current; single-phasing condition; star point connected; three-phase induction motor; winding transformer; zigzag transformer; Circuits; Conductors; Fuses; Helium; Impedance; Induction motors; Power supplies; Stators; Torque; Voltage; Negative-sequence current; single phasing; three-phase induction motor; zero-sequence impedance; zigzag transformer;