    A Novel Approach to Current Transformer Characterization in the Presence of Harmonic Distortion

  • Author

    Cataliotti, Antonio ; Di Cara, Dario ; Emanuel, Alexander E. ; Nuccio, Salvatore

  • Author_Institution
    Dipt. di Ing. Elettr., Elettron. e delle Telecomun., Univ. di Palermo, Palermo
  • Volume
    58
  • Issue
    5
  • fYear
    2009
  • fDate
    5/1/2009 12:00:00 AM
  • Firstpage
    1446
  • Lastpage
    1453
  • Abstract
    The current transformer (CT) performance under distorted waveform conditions is usually characterized by means of the frequency-response test. In this paper, a new way to characterize CTs, closer to real operation conditions, is proposed. The harmonic phase-angle and ratio errors are measured using a nonsinusoidal current composed of fundamental and one harmonic with adjustable phase shift. The new method was tested by determining the performance of two metering class CTs commonly used by the Italian power company. The errors measured using the proposed approach are larger than the ones obtained with the frequency response. This result suggests that the frequency-response approach for the evaluation of CT performance under distorted waveform conditions is not a reliable method.
  • Keywords
    current transformers; harmonic distortion; Italian power company; current transformer characterization; frequency-response test; fundamental-one harmonic; harmonic distortion; harmonic phase-angle; nonsinusoidal current; waveform distortion; Current transformer (CT); frequency response; harmonic distortion; power system harmonics; transducers;
  • fLanguage
    English
  • Journal_Title
    Instrumentation and Measurement, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9456
  • Type

    jour

  • DOI
    10.1109/TIM.2008.2009419
  • Filename
    4749359