DocumentCode :
1066496
Title :
Influence of Specimen Size on the Dielectric Strength of Transformer Oil
Author :
Bell, W.R.
Author_Institution :
Dept. of Electrical Engineering The University of Newcastle upon Tyne, Newcastle upon Tyne, England
Issue :
4
fYear :
1977
Firstpage :
281
Lastpage :
292
Abstract :
The results of some specimen size effect experiments on technical grade transformer oil are reported. Four electrode areas (1.77, 8.19, 37.9 and 177 cm2) and four gap spacings (0 .215 0.464, 1.0 and 2.15 mm) were investigated using a fast ramp (5.5 x 1012 V.cm-1.sec-1) and an ac ramp (12 kV. cm-1.sec-1). Whilst the results are in general agreement with weak link theories, it is suggested that physical specimen size factors play a significant part. Examples of physical size factors are spark conditioning, electrode profile, and liquid motion.
Keywords :
Dielectric breakdown; Dielectric measurements; Distribution functions; Electric breakdown; Electrodes; Oil insulation; Petroleum; Stress; Testing; Vacuum breakdown;