• DocumentCode
    1068495
  • Title

    Calibration of Partial Discharge Detectors for Pulse-Height Distribution Analysis

  • Author

    Ahmed, Abobakr S. ; Zaky, Asser A.

  • Author_Institution
    El-Nasr Company for TV & Elect. Cairo, Egypt
  • Issue
    5
  • fYear
    1979
  • Firstpage
    281
  • Lastpage
    284
  • Abstract
    The effect of the calibration-pulse fall times, ranging from 0.52-56 ¿s, on the response of partial-discharge detectors using a multichannel analyser has been investigated. Although the equalization of fall/rise time ratio results in a single peak distribution, the latter is sensitive to small variations in this ratio. It is shown that a single peak, single-spectrum, can be obtained for ratios of the order of 50.
  • Keywords
    Calibration; Circuits; Detectors; Displays; Impedance measurement; Partial discharges; Pulse measurements; Pulse shaping methods; Pulse transformers; Virtual colonoscopy;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/TEI.1979.298233
  • Filename
    4080662