Abstract :
This paper presents details of the practical implementation of a coordinated reactive power-voltage controller (CQVC) developed for a multi-machine steam power plant. The CQVC performs optimal coordination of the synchronous generators´ reactive power outputs in order to maintain the total reactive power delivered by a steam power plant (SPP) or the voltage at a steam power plant HV busbar. This is required to achieve slow preventive control of generated reactive powers in order to maximize reactive power reserves along with slow high side voltage control. The CQVC is designed to act through existing automatic voltage regulator inputs, thus no modification of an existing excitation system was made. In order to increase the robustness to changes in operating conditions and to achieve the desired shape of the reactive power response, the two-step predictor corrector method is implemented. A newly developed algorithm for steady state detection ensures non-interference of reactive power voltage control with excitation system response. The paper also presents practical design solutions to overcome limitations posed by application to a real system. Acceptance and functional tests carried out during the commissioning of the CQVC are also discussed in this paper.
Keywords :
power plants; predictor-corrector methods; reactive power control; steam power stations; synchronous generators; voltage control; voltage regulators; coordinated QV control; coordinated reactive power voltage controller; excitation system response; multimachine power plant; multimachine steam power plant; optimal coordination; reactive power outputs; slow high side voltage control; steady state detection; steam power plant HV busbar; synchronous generators; two step predictor corrector method; Generators; Power generation; Power system control; Reactive power; Sensitivity; Steady-state; Voltage control; Coordinated Q-V control; predictor-corrector method; sensitivity matrix; steam power plant;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2014.2318794
Filename :
6810864
Link To Document :
بازگشت