DocumentCode
1073065
Title
Corona Discharge Studies in SF6 with Insulators under Positive Switching Impulses
Author
Maller, V.N. ; Srivastava, K.D.
Author_Institution
Electrical Engineering Department University of Waterloo Waterloo, Ontario Canada
Issue
5
fYear
1983
Firstpage
528
Lastpage
535
Abstract
Corona discharge currents and corona inception time delays have been measured in SF6 with an insulating support under positive switching impulses. The insulator surface charging is found to have a significant influence on the corona discharge phenomena. Cumulative probability distribution function of the number of corona pulses is found to depend upon the insulator material and gas pressure. Based on the experimental results, the calculated corona inception time delay distribution with an insulator is found to fit into a log-normal distribution. The influence of insulator on electron initiating mechanism is analyzed using Von Laue diagrams for the corona time delay. The effect of gas pressure and the applied voltage on the inception time delay and pulse current with an insulator in the gap is discussed.
Keywords
Corona; Current measurement; Delay effects; Gas insulation; Log-normal distribution; Probability distribution; Sulfur hexafluoride; Surface charging; Surface discharges; Time measurement;
fLanguage
English
Journal_Title
Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
0018-9367
Type
jour
DOI
10.1109/TEI.1983.298639
Filename
4081148
Link To Document