DocumentCode
1073301
Title
Adaptive noncommunication protection of double-circuit line systems
Author
Bo, Zhiqian Q. ; Dong, Xinzhou Z. ; Caunce, B.R.J. ; Millar, Robin
Author_Institution
ALSTOM T&D Ltd. Protection & Control, Stafford, UK
Volume
18
Issue
1
fYear
2003
fDate
1/1/2003 12:00:00 AM
Firstpage
43
Lastpage
49
Abstract
This paper presents a new technique for noncommunication protection of double-circuit lines. In the technique, the sequence and superimposed signals are used to detect the remote circuit breaker (CB) operation, from which it is to be determined whether a fault inside the protected section can be derived. Extensive simulation studies with respect to typical double-circuit transmission-line systems show that the proposed technique is able to rapidly and correctly determine whether a fault is inside the protected line section without the need for communication links.
Keywords
circuit breakers; power transmission faults; power transmission lines; power transmission protection; adaptive noncommunication protection; double-circuit line systems; double-circuit transmission-line systems; remote circuit breaker operation; sequence signals; superimposed signals; Circuit breakers; Circuit faults; Circuit simulation; Communication channels; Fault detection; Power system protection; Power system reliability; Power system transients; Power transmission lines; Protective relaying;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2002.803748