• DocumentCode
    1073301
  • Title

    Adaptive noncommunication protection of double-circuit line systems

  • Author

    Bo, Zhiqian Q. ; Dong, Xinzhou Z. ; Caunce, B.R.J. ; Millar, Robin

  • Author_Institution
    ALSTOM T&D Ltd. Protection & Control, Stafford, UK
  • Volume
    18
  • Issue
    1
  • fYear
    2003
  • fDate
    1/1/2003 12:00:00 AM
  • Firstpage
    43
  • Lastpage
    49
  • Abstract
    This paper presents a new technique for noncommunication protection of double-circuit lines. In the technique, the sequence and superimposed signals are used to detect the remote circuit breaker (CB) operation, from which it is to be determined whether a fault inside the protected section can be derived. Extensive simulation studies with respect to typical double-circuit transmission-line systems show that the proposed technique is able to rapidly and correctly determine whether a fault is inside the protected line section without the need for communication links.
  • Keywords
    circuit breakers; power transmission faults; power transmission lines; power transmission protection; adaptive noncommunication protection; double-circuit line systems; double-circuit transmission-line systems; remote circuit breaker operation; sequence signals; superimposed signals; Circuit breakers; Circuit faults; Circuit simulation; Communication channels; Fault detection; Power system protection; Power system reliability; Power system transients; Power transmission lines; Protective relaying;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2002.803748
  • Filename
    1159895