Experimental facility for investigation of lightning performance of distribution lines
Author :
Nakada, Kazuo ; Sugimoto, Hitoshi ; Yokoyama, Shigeru
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Hokuriku Electr. Power Co., Tokyo, Japan
Volume :
18
Issue :
1
fYear :
2003
fDate :
1/1/2003 12:00:00 AM
Firstpage :
253
Lastpage :
257
Abstract :
In order to clarify the lightning performance of a distribution line, test distribution lines and a test tower were constructed at the Mikuni Testing Center of Hokuriku Electric Power Company in 1999. Using these facilities, the authors observed transient voltages and current distributions due to direct strokes of natural lightning. Based on this data, we have clarified the following points: (1) calculated voltages and currents using the EMTP agree with the experimental results fairly well; and (2) for lightning currents of long durations, however, the reduction of voltages across arresters by energy absorption should be taken into consideration.
Keywords :
EMTP; current distribution; power distribution faults; power distribution lines; power distribution protection; power system analysis computing; power system measurement; power system transients; test facilities; ENITP; Japan; current distributions; distribution lines lightning performance; test distribution lines; test tower; transient voltages; Arresters; Current distribution; EMTP; Grounding; Lightning; Poles and towers; Power system transients; Surges; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2002.803844
Filename :
1159927
Link To Document :
بازگشت