Title :
Signatures of voltage dips: transformer saturation and multistage dips
Author :
Styvaktakis, Emmanouil ; Bollen, Math H J
Author_Institution :
Dept. of Electr. Power Eng., Chalmers Univ. of Technol., Gothenburg, Sweden
fDate :
1/1/2003 12:00:00 AM
Abstract :
Obtaining information on the voltage dips that occur in a network is one of the most important tasks of a power quality monitoring program. This paper focuses on two types of voltage dips that although mentioned in the literature, their characteristics have not been presented before. These types are: voltage dips due to transformer saturation and multistage voltage dips due to faults (dips that present more than one stages of voltage magnitude before the fault clearing operation). Simulations and real measurements are used to show the features of these types of phenomena. Overall, the paper offers the means for a systematic processing of the measurements obtained by power quality monitors.
Keywords :
power supply quality; power system faults; power system measurement; power system transients; power transformers; measurements processing; multistage voltage dips; power quality monitoring program; transformer saturation; voltage dips signatures; Circuit faults; Electronics packaging; Monitoring; Power quality; Power system faults; Power system measurements; Power system simulation; Power systems; Power transformers; Voltage fluctuations;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2002.804016