• DocumentCode
    1074453
  • Title

    Assessment of the Impact of Joint Bays on the Ampacity of High-Voltage Cable Circuits

  • Author

    Pilgrim, James A. ; Swaffield, David J. ; Lewin, Paul L. ; Larsen, S.T. ; Payne, D.

  • Author_Institution
    Univ. of Southampton, Southampton
  • Volume
    24
  • Issue
    3
  • fYear
    2009
  • fDate
    7/1/2009 12:00:00 AM
  • Firstpage
    1029
  • Lastpage
    1036
  • Abstract
    Improvements in the cost and availability of computational power in recent years has led to numerical techniques such as finite-element analysis (FEA) becoming viable for cable-rating calculations. This analysis has previously been completed for the case of directly buried and force-cooled cable circuits, but without direct consideration of the joint bay. This paper presents methods by which conductor temperature profiles within joint bays may be obtained through the use of FEA. Results are presented for a number of joint bay configurations common to the U.K. for naturally and force-cooled installations. Implications of the results on circuit-rating practice are discussed and the benefits of using tools, such as FEA, are considered versus other existing methods.
  • Keywords
    finite element analysis; power cables; U.K; cable-rating calculations; conductor temperature; directly buried cable circuits; finite element analysis; force-cooled cable circuits; force-cooled installations; high-voltage cable circuits; joint bays; numerical techniques; Finite-element methods; power cable connecting; power cable thermal factors;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2009.2021084
  • Filename
    5075516