  • Abstract
    The author describes an approach used in Russia to develop diagnostic techniques to assess the condition of oil-filled power equipment. He considers that the most useful parameters to estimate remaining life are the partial pressures of dissolved gases and water in the oil and the water content in the solid insulation. Gas chromatography is used to determine these parameters from oil samples taken from equipment in service.
  • Keywords
    bushings; chemical analysis; chromatography; condition monitoring; insulation testing; power cable insulation; power cable testing; power capacitors; power transformer insulation; power transformer testing; remaining life assessment; transformer oil; Russia; bushings; cables; capacitors; condition assessment; diagnostic techniques; dissolved gases; gas chromatography; oil-filled power equipment; partial pressures; remaining life estimation; solid insulation; transformers; water content; water in oil; Aging; Cable insulation; Chemical compounds; Dielectric liquids; Dielectrics and electrical insulation; Gas insulation; Gases; Oil insulation; Petroleum; Power transformer insulation;