Title :
A Complete Strategy for Conducting Dynamic Contact Resistance Measurements on HV Circuit Breakers
Author :
Landry, Michel ; Turcotte, Olivier ; Brikci, Fouad
Author_Institution :
Hydro-Quebec´´s Res. Inst., Varennes
fDate :
4/1/2008 12:00:00 AM
Abstract :
Dynamic contact resistance measurement (DRM) is known as an effective technique for assessing the condition of power circuit-breaker (CB) main contacts and arcing contacts. In some SF6 gas CBs, the metallic fluorides (white or gray powder) produced during the arc quenching process mask the actual breaker contact resistance. In this case, the standard DRM method of injecting 100 A dc is no longer applicable. The following paper proposes a complete strategy for conducting DRM on high-voltage CBs based on three relevant parameters: breaker contact speed (low or rated), injected current values (100-2800 A dc), and the presence of metallic fluorides deposited on breaker contacts.
Keywords :
SF6 insulation; circuit breakers; contact resistance; gas insulated switchgear; HV circuit breakers; SF6 gas; arc quenching process; dynamic contact resistance measurements; metallic fluorides; Arc byproducts; circuit breakers (CBs); dynamic contact resistance measurement; metallic fluorides;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2008.917694