• DocumentCode
    1076189
  • Title

    Contribution on the Specification of an Aging Test for the Insulation of Enclosed, Air-Insulated Switchgear

  • Author

    Koenig, D. ; Roesch, P. ; Mueller, B.

  • Author_Institution
    Technical University of Darmstadt High Voltage Laboratory Darmstadt, Federal Republic of Germany
  • Issue
    6
  • fYear
    1987
  • Firstpage
    769
  • Lastpage
    774
  • Abstract
    Because of high humidity and condensation, layers of moisture are formed on the surface of insulating materials in indoor switchgear installations which, as a result of contamination, are conductive electrolytic boundary layers. When this happens, electrochemical interactions can produce aging of the insulating material surfaces that may even lead to failure of the insulation. Basic investigations were carried out on a rod-shaped model insulator with simul taneous subjection to an electric field, moisture, and polution. Electrical, chemical, and optical diagnostic methods make it possible to determine aging related surface changes. Based on these results and taking into account the results of work done by the International Working Group IEC-SC17/WGIO "Aging Tests", proposals are discussed for an aging test for enclosed indoor switchgear. In particular, procedures are discussed for simulating the aging phenomena with time compression. The suitability or nonsuitability of individual parameters are discussed.
  • Keywords
    Aging; Chemicals; Conducting materials; Dielectrics and electrical insulation; Humidity; Insulation testing; Moisture; Optical materials; Surface contamination; Switchgear;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/TEI.1987.298939
  • Filename
    4081484