DocumentCode
1077345
Title
Large Scale Dielectric Test of Transformer Oil with Uniform Field Electrodes
Author
Simo, E.
Author_Institution
Ferranti-Packard Ltd., Toronto, Ont., Canada
Issue
4
fYear
1970
Firstpage
121
Lastpage
126
Abstract
Results of 60-Hz breakdown tests of transformer oil obtained with 3-, 15-, and 30-cm-diameter brass, copper, and aluminum electrodes are analyzed. The influence of the electrode area as well as the influence of different electrode materials is shown. It is suggested that for evaluation purposes of transformer oil, the statistical occurrence of the minimum, mean, and maximum values should be applied instead of the test values obtained with American Society for Testing Materials (ASTM), British Standards (BS), or Verein Deutscher Elektrotechniker (VDE) tests.
Keywords
Aluminum; Dielectrics; Electric breakdown; Electrodes; Impurities; Large-scale systems; Materials testing; Oil insulation; Petroleum; Shape;