The use of distribution bus var to improve transmission power quality - Forgoing Flicker
Author :
Thomas, Edward S.
Author_Institution :
Utility Electr. Consultants, Raleigh
Volume :
13
Issue :
4
fYear :
2007
Firstpage :
34
Lastpage :
41
Abstract :
This article reviews the application of an adaptive var compensator (AVC) to reduce voltage flicker associated with the starting of large motors. The case considered here involves the sequential starting of two 2,000-hp motors in an across-the-line mode. The motors are served by a dedicated 44 kV- 4.16 kV substation. The source 44-kV transmission line also serves over 7,000 residential and commercial customers through two widely separated 44 kV-12.5 kV substations. Several methods of reducing flicker were considered. Customer complaints associated with voltage excursions during motor starting were successfully resolved.
Keywords :
electric motors; power supply quality; adaptive var compensator; commercial customers; customer complaints; large motor starting; motor sequential starting; residential customers; substation; transmission line; voltage excursions; voltage flicker reduction; Capacitors; Frequency; Impedance; Petroleum; Power quality; Power transmission lines; Reactive power; Springs; Substations; Voltage fluctuations;