DocumentCode
1083738
Title
Measured and predicted cold load pick up and feeder parameter determination using the harmonic model algorithm
Author
Law, John ; Minford, Donald ; Elliott, Larry ; Storms, Michael
Author_Institution
Idaho Univ., Moscow, ID, USA
Volume
10
Issue
4
fYear
1995
Firstpage
1756
Lastpage
1764
Abstract
This paper presents theory of the "cold load harmonic", CLHARM, model algorithm for simulation of power feeder currents resulting from both cold load pickup, CLPU, and the "step voltage test", STEPV. The STEPV method is also presented. Feeder parameters obtained from field STEPV measurement are used to predict CLPU on that feeder using the CLHARM algorithm. STEPV test measurements and actual measured CLPU currents on the same feeder are compared with computer predictions. The CLHARM aggregates feeder thermostatically controlled load to simulate regain of diversity during outage restoration. All feeder weather sensitive load is lumped in CLHARM, using mean parameter values of a simple thermodynamic model. The ultimate objective of this work is experimentally obtained feeder "signatures" for CLPU prediction as a feeder design tool.
Keywords
distribution networks; power system analysis computing; power system harmonics; power system measurement; power system restoration; cold load harmonic; cold load pick up; computer simulation; feeder parameter determination; harmonic model algorithm; outage restoration; power feeder currents; step voltage test measurement; thermodynamic model; thermostatically controlled load; weather sensitive load; Costs; Current measurement; Power measurement; Power system harmonics; Power system modeling; Predictive models; Resistance heating; Testing; Voltage; Weather forecasting;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.476039
Filename
476039
Link To Document