DocumentCode
1084416
Title
Method for reliability analysis of industrial distribution systems
Author
Bollen, M.H.J.
Author_Institution
Group of Electr. Energy Syst., Eindhoven Univ. of Technol., Netherlands
Volume
140
Issue
6
fYear
1993
fDate
11/1/1993 12:00:00 AM
Firstpage
497
Lastpage
502
Abstract
The method for reliability analysis of industrial distribution systems presented in this paper combines a Monte Carlo simulation with an electrical network model. The Monte Carlo simulation generates fail and restore events in stochastic components. The flexibility of the Monte Carlo simulation made it possible to include ageing of components and preventive maintenance. As industrial loads are often sensitive to short duration voltage sags, the influence of these sags had to be included in the model. This is done by using the maximum permissible voltage sag at the load nodes as an interruption criterion. The occurrence of a short-circuit and the intervention by the protection are modelled in detail. Mal-trips as well as fail-to-trip of the protection are included. The method presented in this paper is suitable for industrial (and other) distribution systems where sensitive loads are present, where maintenance of components is important and/or where the behaviour of the protection influences the reliability
Keywords
Monte Carlo methods; distribution networks; industries; load (electric); power system protection; power system reliability; relay protection; Monte Carlo simulation; ageing; electrical network model; fail-to-trip; false tripping; industrial distribution systems; interruption criterion; load nodes; power system protection; preventive maintenance; reliability analysis; sensitive loads; short-circuit; stochastic components; voltage sags;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings C
Publisher
iet
ISSN
0143-7046
Type
jour
Filename
285165