Title :
Three terminal line protection based on a superimposed component impedance relay
Author :
Daniel, J.S. ; Aggarwal, R.K. ; Johns, A.T.
Author_Institution :
Dept. of Electr. & Electron. Eng., Newcastle upon Tyne Univ., UK
fDate :
11/1/1993 12:00:00 AM
Abstract :
The paper presents the application of a new impedance relaying principle to a Teed feeder. The relay design is immune from false tripping owing to power swings or prefault load conditions. This has been achieved by extracting and using prefault and superimposed components of relaying voltages and currents. Results are presented for earth faults on a Teed feeder configuration. Relay trip time is typically in the range 11 to 20 ms and is plotted as a surface against prefault power angle and fault point on wave angle
Keywords :
distribution networks; earthing; electrical faults; power system protection; relay protection; 11 to 20 ms; Teed feeder; design; earth faults; fault point on wave angle; power swings; power system protection; power transmission lines; prefault load conditions; prefault power angle; superimposed component impedance relay; trip time;
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings C