DocumentCode :
1085032
Title :
Sensitivity studies on power transformer ferroresonance of a 400 kV double circuit
Author :
Charalambous, C. ; Wang, Z.D. ; Osborne, M. ; Jarman, P.
Author_Institution :
Sch. of Electr. & Electron. Eng., Univ. of Manchester, Manchester
Volume :
2
Issue :
2
fYear :
2008
fDate :
3/1/2008 12:00:00 AM
Firstpage :
159
Lastpage :
166
Abstract :
The ability to predict ferroresonance significantly relies on the accuracy of the transformer model and the power system´s parameters. The accomplishment of a suitable simulation model allows the sensitivity studies to be performed to determine the degree of influence of various components and parameters of the ferroresonance phenomenon such as line length, point-on-wave switching and transformer core loss. The modelling work carried out in ATP (commercially available software) on a 1000 MVA 400/275/13 kV power transformer model is described and the simulation with field ferroresonance test recordings is verified. The maps that define the boundaries between safe and ferroresonant (fundamental, subharmonic, chaotic) regions as a function of system parameters are created through the sensitivity studies performed.
Keywords :
ferroresonance; power transformers; sensitivity analysis; apparent power 1000 MVA; double-circuit configuration; point-on-wave switching; power transformer ferroresonance; sensitivity studies; transformer core loss; voltage 400 kV;