DocumentCode :
1088296
Title :
Equal-area criterion: an extension for multimachine power systems
Author :
Haque, M.H.
Author_Institution :
Dept. of Electr. Eng., King Fahd Univ. of Pet. & Miner., Dhahran, Saudi Arabia
Volume :
141
Issue :
3
fYear :
1994
fDate :
5/1/1994 12:00:00 AM
Firstpage :
191
Lastpage :
197
Abstract :
A method of determining the transient stability of a multimachine power system through a modified equal-area criterion is proposed. The method determines the first-swing stability limit of the most severely disturbed machine in the system by comparing two integrals or areas called the accelerating and decelerating areas. Unlike the standard equal-area criterion, the proposed method can be directly applied to a multimachine power system without representing the system by an equivalent single-machine infinite-bus model. The proposed method was tested on three power networks for a number of different faults. The critical clearing time obtained by the proposed method in each case was compared with the actual value found by the step-by-step method.<>
Keywords :
electrical faults; power system stability; power system transients; accelerating area; critical clearing time; decelerating area; equal-area criterion; faults; first-swing stability limit; modified equal-area criterion; multimachine power systems extensions; severely disturbed machine; step-by-step method; transient stability;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:19949871
Filename :
285774
Link To Document :
بازگشت