• DocumentCode
    1090209
  • Title

    Inferring ceramic insulator pollution by an innovative approach resorting to PD detection

  • Author

    Cavallini, Andrea ; Chandrasekar, S. ; Montanari, Gian ; Puletti, Francesco

  • Author_Institution
    LIMAT, Bologna Univ.
  • Volume
    14
  • Issue
    1
  • fYear
    2007
  • Firstpage
    23
  • Lastpage
    29
  • Abstract
    This paper presents a technique for outdoor ceramic insulator pollution assessment based on partial discharge detection and analysis. Laboratory tests and data coming from a monitoring activity carried out on some insulators of transmission lines are reported. They support the effectiveness of partial discharge detection and analysis as a tool to carry out condition-based maintenance of insulators of overhead lines. In particular, it can be seen that partial discharge analysis highlights the mechanisms bringing insulators to flashover (dry band arc activity) and is, therefore, well suited to predict increasing pollution and imminent flashover. As a consequence, algorithms are proposed to provide a quantitative evaluation of pollution severity
  • Keywords
    ceramic insulators; flashover; insulator contamination; partial discharge measurement; power overhead lines; PD detection; ceramic insulator pollution; condition-based maintenance; flashover; overhead transmission lines; partial discharge detection; Arc discharges; Ceramics; Flashover; Insulation; Insulator testing; Laboratories; Leakage current; Partial discharges; Pollution; Surface contamination;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2007.302866
  • Filename
    4088907