DocumentCode :
1093220
Title :
Communication after Adjournment
Author :
Floy, Henry
fYear :
1903
Firstpage :
297
Lastpage :
297
Abstract :
Fearing tlhat the remarks of some of the speakers may have left an erroneous impression as to the potential of telephone circuits carried on the poles of high-tension transmission lines, I desire to state that some measurements made by a Weston voltmeter between the conductors of a telephone circuit placed five feet below the conductors of a 25,000 volt overhead circuit and ground, showed tlhe potential to be only from 140 to 160 volts. Similar measurements on a telephone circuit three feet below a 10,000 volt line showed only about 95 volts to ground and, naturally, no difference of potential between the telephone conductors. It seems to me that the voltage of a telephone circuit given as 20,000 by Mr. Thomas cannot be such potential as would be indicated by a voltmeter or such as would cause particular damage, being, I assume, simply static potential. Referring to the suggestions made as to signaling in case of partial breakdown of the telephone system, it has occurred to me that as a relay to the telephone circuit, a system of wireless telegraphy could be installed without large expense, which might advantageouslv be used in transmitting signals in case of trouble with tlhe telephone circuit.
Keywords :
Conductors; Distributed parameter circuits; Electric breakdown; Power overhead lines; Relays; Telegraphy; Telephony; Transmission line measurements; Voltage; Voltmeters;
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
Publisher :
ieee
ISSN :
0096-3860
Type :
jour
DOI :
10.1109/T-AIEE.1903.4764306
Filename :
4764306
Link To Document :
بازگشت