DocumentCode :
1094853
Title :
Maximum insulation stresses under transient voltages in the HV barrel-type winding of distribution and power transformers
Author :
Mazur, Alexander ; Kerszenbaum, Isidoro ; Frank, Jerome
Author_Institution :
Int. Transformer Corp., Montebello, CA, USA
Volume :
24
Issue :
3
fYear :
1988
Firstpage :
427
Lastpage :
433
Abstract :
Analytical as well as experimental results are presented for voltages developed in HV (high-voltage) windings of dry-tyre power and distribution transformers when subjected to surge transients. Although the existence of this phenomenon has been known for years, it has not always been taken into consideration in the calculation of insulation stresses. The possibility of accurate prediction of the developed voltages is demonstrated
Keywords :
power transformers; transformer windings; transients; HV barrel-type winding; distribution transformers; maximum insulation stresses; power transformers; surge transients; Capacitance; Electrical equipment industry; Equations; Inductance; Power system transients; Power transformer insulation; Stress; Surges; Voltage; Windings;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/28.2891
Filename :
2891
Link To Document :
بازگشت