• DocumentCode
    1095514
  • Title

    Evaluation of the voltage change factor kU for DG equipped with synchronous generators

  • Author

    Kasmas, N.A. ; Papathanassiou, S.A.

  • Author_Institution
    Distrib. Div., Public Power Corp., Athens
  • Volume
    2
  • Issue
    2
  • fYear
    2008
  • fDate
    6/1/2008 12:00:00 AM
  • Firstpage
    102
  • Lastpage
    112
  • Abstract
    An evaluation of the voltage disturbances caused by the synchronisation to the grid of distributed generation (DG) resources equipped with synchronous generators is presented. The synchronisation procedures and the resulting transients are first discussed. The effect of the synchronisation conditions (frequency, phase, voltage magnitude deviations) on the resulting fast voltage changes is then demonstrated through an extensive set of simulations. The investigation is extended to the effect of other parameters of the grid and the generator. Objective of the analysis is to shed some light on the selection of appropriate values for the voltage change factor k U, as per IEC 61400-21, which is used in practical situations to evaluate the fast voltage changes due to the connection of DG power stations.
  • Keywords
    IEC standards; distributed power generation; fault diagnosis; power grids; power stations; synchronous generators; DG; IEC 61400-21; distributed generation resources; synchronisation conditions; synchronous generators; voltage change factor evaluation;
  • fLanguage
    English
  • Journal_Title
    Renewable Power Generation, IET
  • Publisher
    iet
  • ISSN
    1752-1416
  • Type

    jour

  • DOI
    10.1049/iet-rpg:20070015
  • Filename
    4469296