• DocumentCode
    109562
  • Title

    Nontraditional Relay Curves for the Coordination of the Ground Overcurrent Function With Downstream Fuses

  • Author

    Sorrentino, Elmer

  • Author_Institution
    Univ. Simon Bolivar, Caracas, Venezuela
  • Volume
    29
  • Issue
    3
  • fYear
    2014
  • fDate
    Jun-14
  • Firstpage
    1284
  • Lastpage
    1291
  • Abstract
    This paper describes the details for the application of some nontraditional relay curves for the coordination of the ground overcurrent function with downstream fuses. These curves have a segmented shape in order to achieve the best combination of sensitivity, speed, and selectivity. For this segmented shape, greater current does not necessarily imply a shorter time. These curves can be programmed in different ways, according to the available features in the commercial relays, and the expected behavior of two options is analyzed. Both options would have satisfactory behavior although they would have different dynamic behavior.
  • Keywords
    earthing; electric fuses; power distribution protection; relay protection; commercial relays; distribution system protection; downstream fuse; dynamic behavior; ground overcurrent function; nontraditional relay curve; overcurrent relay fuse coordination; Circuit breakers; Circuit faults; Fault currents; Fuses; Relays; Sensitivity; Shape; Ground overcurrent protection; overcurrent relay-fuse coordination; protection of distribution systems;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2013.2288134
  • Filename
    6746136