Abstract
This paper describes the details for the application of some nontraditional relay curves for the coordination of the ground overcurrent function with downstream fuses. These curves have a segmented shape in order to achieve the best combination of sensitivity, speed, and selectivity. For this segmented shape, greater current does not necessarily imply a shorter time. These curves can be programmed in different ways, according to the available features in the commercial relays, and the expected behavior of two options is analyzed. Both options would have satisfactory behavior although they would have different dynamic behavior.
Keywords
earthing; electric fuses; power distribution protection; relay protection; commercial relays; distribution system protection; downstream fuse; dynamic behavior; ground overcurrent function; nontraditional relay curve; overcurrent relay fuse coordination; Circuit breakers; Circuit faults; Fault currents; Fuses; Relays; Sensitivity; Shape; Ground overcurrent protection; overcurrent relay-fuse coordination; protection of distribution systems;