• DocumentCode
    1097435
  • Title

    Testing of a Resistive Fault Current Limiter Component Based on Bi-2212 Bifilar Coil

  • Author

    Polasek, A. ; Sena, C.V. ; Dias, R. ; Serra, E.T. ; Rizzo, F.C.

  • Author_Institution
    CEPEL-Electr. Power Res. Center, Rio de Janeiro, Brazil
  • Volume
    19
  • Issue
    3
  • fYear
    2009
  • fDate
    6/1/2009 12:00:00 AM
  • Firstpage
    1823
  • Lastpage
    1826
  • Abstract
    A shunted bulk Bi-2212 bifilar coil was cooled with liquid nitrogen (77 K) and subjected to controlled fault current tests. Prospective currents achieving 11 kA were limited to about 5 kA (first peak) and to 3 kA (following peaks), under 200-300 V. The Bi-2212 coil was able to withstand several short circuits, showing a fast response and reproducible results. A recovery time of minutes was needed between two successive tests. Therefore, the bulk coil was damaged when the interval between subsequent short-circuits was reduced to 30-60 seconds. The critical current was severely reduced by those last tests and further thermal shock. The bulk coil was cut in transversal and longitudinal sections, in order to evaluate the damages.
  • Keywords
    coils; fault current limiters; short-circuit currents; testing; thermal shock; current 11 kA; current 3 kA; current 5 kA; fault current test; resistive fault current limiter component testing; short circuit current; shunted bulk Bi-2212 bifilar coil; thermal shock; time 30 s to 60 s; voltage 200 V to 300 V; Bi-2212; Bifilar coil; bulk; fault current limiter;
  • fLanguage
    English
  • Journal_Title
    Applied Superconductivity, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1051-8223
  • Type

    jour

  • DOI
    10.1109/TASC.2009.2017753
  • Filename
    5109531