• DocumentCode
    1098475
  • Title

    Wide-Area Detection of Voltage Instability From Synchronized Phasor Measurements. Part I: Principle

  • Author

    Glavic, Mevludin ; Van Cutsem, Thierry

  • Author_Institution
    Dept. of Electr. Eng. & Comput. Sci., Univ. of Liege, Liege, Belgium
  • Volume
    24
  • Issue
    3
  • fYear
    2009
  • Firstpage
    1408
  • Lastpage
    1416
  • Abstract
    This two-part paper deals with the early detection of an impending voltage instability from the system states provided by synchronized phasor measurements. Recognizing that voltage instability detection requires assessing a multidimensional system, the method fits a set of algebraic equations to the sampled states, and performs an efficient sensitivity computation in order to identify when a combination of load powers has passed through a maximum. The important effects of overexcitation limiters are accounted for. The approach does not require any load model. This first part of the paper is devoted to theoretical foundations of sensitivity calculation along the system trajectory, derivation of the algebraic model, and illustration on a simple five-bus system involving the long-term dynamics of a load tap changer and a field current limiter.
  • Keywords
    algebra; current limiters; on load tap changers; phase measurement; power system measurement; algebraic equations; field current limiter; five-bus system; load tap changer; long-term dynamics; multidimensional system; overexcitation limiters; sensitivity computation; synchronized phasor measurements; wide-area voltage instability detection; Instability detection; long-term voltage stability; phasor measurement units; sensitivity analysis; wide-area monitoring;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2009.2023271
  • Filename
    5109626