Title :
Improving the Specifications for Power-Line Filters
Author :
Milton, Jules ; Greenwood, Edward
Author_Institution :
Filtron Company, Inc., a subsidiary of Liquidonics Industries, Inc., Flushing, N. Y. 11355
fDate :
6/1/1968 12:00:00 AM
Abstract :
The most important requirement of a power-line filter is its insertion loss under load. This paper discusses methods of extending and improving the technique of measuring insertion loss as specified in MIL-STD-220A. It discusses present equipment limitations in MIL-STD-220A that restricts full-load tests to frequencies above 100 kHz and limits maximum current to 100 amperes. However, it is realized that MIL-STD-220A is the only available specification at present. Therefore, the paper discusses methods of extending the MIL-STD-220A technique for measuring the insertion loss of filters for frequencies as low as 14 kHz and under loads as high as 200 amperes. A new buffer network that allows such measurements is described. In addition, a method is discussed for improving voltage regulation and reducing distortion of the power-line waveshape caused by power filters. These are two parameters which have been totally ignored when specifying power filters and which have been found to cause considerable electrical problems after installation.
Keywords :
Attenuation measurement; Distortion measurement; Frequency measurement; Insertion loss; Loss measurement; Military communication; Performance evaluation; Power filters; Testing; Voltage control;
Journal_Title :
Electromagnetic Compatibility, IEEE Transactions on
DOI :
10.1109/TEMC.1968.302960