• DocumentCode
    1101041
  • Title

    Evaluation of Thermal Transient and Overload Capability of High-Voltage Bushings With ATP

  • Author

    Zhang, Shibao

  • Author_Institution
    PCore Electr. Co. Inc., LeRoy, NY
  • Volume
    24
  • Issue
    3
  • fYear
    2009
  • fDate
    7/1/2009 12:00:00 AM
  • Firstpage
    1295
  • Lastpage
    1301
  • Abstract
    In this paper, the alternative transient program is used to solve the thermal network for high-voltage bushings in which the thermal capacitance is the key component leading to the thermal transient as it reflects the capability of a material to store energy. The modeling method is discussed. The test and simulation results are in good agreement for the thermal steady state and transient of the bushings. The transient results are then used to evaluate the bushing overload capability.
  • Keywords
    bushings; capacitance; power system transients; alternative transient program; high voltage bushings; overload capability; thermal capacitance; thermal network; thermal steady state; thermal transient; Capacitance; Insulators; Oil insulation; Petroleum; Power transformer insulation; Steady-state; Temperature; Testing; Thermal loading; Thermal resistance; Alternative Transient Program (ATP); bushing; modeling; overload capability; steady state; thermal capacitance; thermal transient;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2009.2014484
  • Filename
    5109879