DocumentCode :
1103052
Title :
Heat transfer in forced cooled cables
Author :
Lombardi, A. ; Donazzi, F. ; Taralli, C. ; Tencer, C. ; Lima, A.J.O.
Author_Institution :
Societa Cavi Pirelli, Milan, Italy
Volume :
5
Issue :
1
fYear :
1990
fDate :
1/1/1990 12:00:00 AM
Firstpage :
8
Lastpage :
13
Abstract :
A calculation method is presented for continuous rating of cable lines. The method takes into account the actual environment conditions, such as different types of soil, change of geometrical disposition, etc. This method is based on the resolution in terms of limit differences. The results for a full-scale experimental installation were used to check the theoretical model. Comparison between the measured and calculated rises showed a difference of 5% in general and a maximum of 7%, which may be considered acceptable for line design
Keywords :
cooling; heat transfer; power cables; continuous rating; environment conditions; forced cooled cables; geometrical disposition; heat transfer; limit differences; soil types; Cables; Conductors; Coolants; Cooling; Dielectric losses; Equations; Heat transfer; Soil; Temperature; Thermal resistance;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.107248
Filename :
107248
Link To Document :
بازگشت