DocumentCode :
1103156
Title :
Construction of 8000 A class 275 kV gas insulated transmission line
Author :
Kuroyanagi, Y. ; Toya, A. ; Hayashi, T. ; Araki, T.
Author_Institution :
Tokyo Electr. Power Co. Inc., Japan
Volume :
5
Issue :
1
fYear :
1990
fDate :
1/1/1990 12:00:00 AM
Firstpage :
14
Lastpage :
20
Abstract :
Class-8000 A 275 kV gas insulated transmission lines (GIL), 138 m and 158 m long, were completed as getaway lines in the Shin Noda substation of the Tokyo Electric Power Co. Inc. in March and May 1988, respectively. The GILs were designed for large current capacity. New techniques used to construct these lines are described. Thermal expansion and contraction of a straight section of a GIL is absorbed by varying the angle of a deflection unit. Supports were designed to absorb a ground depression. GIL units were installed with gantry cranes. Joints of enclosures were welded by an automatic welding machine
Keywords :
cable jointing; gaseous insulation; power transmission lines; substations; 138 m; 158 m; 275 kV; 8000 A; GIL; Shin Noda substation; Tokyo Electric Power Co. Inc.; automatic welding machine; gas insulated transmission lines; joints; supports; thermal contraction; thermal expansion; Conductors; Cranes; Gas insulated transmission lines; Ground support; Insulation; Power transmission lines; Substations; Thermal conductivity; Thermal expansion; Welding;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.107249
Filename :
107249
Link To Document :