DocumentCode
1103158
Title
The Calibration of Current Transformers by Means of Mutual Inductances
Author
Fortescue, Charles
Issue
2
fYear
1915
fDate
7/1/1915 12:00:00 AM
Firstpage
1599
Lastpage
1626
Abstract
Reasons are given for the selection of mutual inductances as a means for calibrating current transformers, the most important of which is the wide use to which they may be put besides the calibration of current transformers. The design and manufacture of the apparatus are described, reasons being given for the choice of the form of the secondary coil of the mutual inductance, which is a uniformly wound ring, and of the material used for the core, namely, marble. The formula used in calculating the values of mutual inductance is given and its limitations stated. Variations in physical dimensions are given and errors in calculated value discussed. The method of calibrating the mutual inductances is described, which illustrates also one method of using the apparatus for measuring mutual inductance. The method of measuring ratios and phase displacements by means of the apparatus, and the merits of various instruments for obtaining a balance, are described and discussed. An artificial method of loading the transformers under test is proposed. Its advantages are pointed out. The use of the apparatus for measuring mutual inductance, self-inductance and alternating-current resistance is described. In conclusion it is stated that the apparatus has been satisfactory, and has given little difficulty in manufacture.
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1915.4765274
Filename
4765274
Link To Document