DocumentCode
1104629
Title
Field evaluation of industry´s first self-protected, light-triggered thyristor
Author
Cibulka, Frank ; Crane, Lynn ; Marks, John
Author_Institution
Westinghouse Electr. Corp., Pittsburgh, PA, USA
Volume
5
Issue
1
fYear
1990
fDate
1/1/1990 12:00:00 AM
Firstpage
110
Lastpage
116
Abstract
A description is given of the industry´s first self-protected, light-triggered thyristor to be developed, fabricated, and field-demonstrated. This device is installed on a 13.8 kV, 40 MVAr AC switch using 16 series-connected devices operating in one phase of a static VAr compensator at the Minnesota Power Co.´s Shannon substation. The light-triggered thyristor was designed with internal overvoltage protection (safe turn-on at a preset overvoltage level) and with significantly improved dv /dt withstand characteristics. In the process, the AC switch in the static VAr compensator was redesigned to incorporate 16 instead of the originally installed 24 series-connected thyristors
Keywords
static VAr compensators; switches; thyristor applications; 13.8 kV; 40 MVAr; Minnesota Power Co.; Shannon substation; internal overvoltage protection; safe turn-on; self-protected light-triggered thyristor; static VAr compensator; Circuits; Cranes; Power system protection; Static VAr compensators; Substations; Switches; Textile industry; Thyristors; Valves; Voltage control;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.107262
Filename
107262
Link To Document