DocumentCode
1105229
Title
Lightning overvoltage protection of the Paddock 362-145 kV gas-insulated substation
Author
Elahi, H. ; Sublich, M. ; Anderson, M.E. ; Nelson, B.D.
Author_Institution
GE Ind. & Utility Sales, Schenectady, NY, USA
Volume
5
Issue
1
fYear
1990
fDate
1/1/1990 12:00:00 AM
Firstpage
144
Lastpage
150
Abstract
Backflashovers close to the Paddock 362-145 kV gas-insulated substation (GIS) have been analyzed with the electromagnetic transient program (EMPT) using a frequency-dependent multiconductor system. The severities of the lightning stroke currents were based on recent recordings in the eastern United States. The effects of corona attenuation and distortion were accounted for using a shunt linear model approach. Turn-up effects of both line insulator flashover voltages and surge arrester protective characteristics were based on manufacturer´s volt-time curves. Wave-shaping effects of substation capacitances were modeling details in determining the overvoltages inside the GIS due to close backflashovers, which are caused by lightning strokes with varying intensity. These results are aimed at better evaluation of lighting protection requirements for GIS protected by metal-oxide surge arresters
Keywords
corona; flashover; gaseous insulation; overvoltage protection; substations; surge protection; 362 to 145 kV; EMPT; GIS; Paddock gas-insulated substation; close backflashovers; corona attenuation; corona distortion; electromagnetic transient program; frequency-dependent multiconductor system; lightning stroke currents; line insulator flashover voltages; shunt linear model; substation capacitances; surge arrester protective characteristics; Arresters; Corona; EMTP; Electromagnetic analysis; Frequency; Geographic Information Systems; Lightning; Substation protection; Surge protection; Voltage control;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.107267
Filename
107267