Abstract
It is possible to design SF6 autoexpansion breakers which are free from critical currents. In these devices, which combine arc rotation in a magnetic field and thermal expansion of gas, critical currents can effectively occur if these effects are incorrectly created and combined. An analytic and experimental method optimizing the current at which rotation should start is presented. The study of the gas flow then ensures coupling with expansion. These investigations lead to representation of a thermal time constant directly related to interrupting capacity
Keywords
circuit breakers; gaseous insulation; sulphur compounds; SF6 autoexpansion breaker; arc rotation; critical current; gas flow; interrupting capacity; magnetic arc control; thermal time constant; Coils; Inductors; Magnetic fields; Threshold current;